Vacon NXP Wall-mounted
Vacon NXP (NX professional series) wall-mounted VFD is a compact and comprehensive drive package. Engineered with all the necessary components, integrated into a single frame. The NXP drives are designed to handle high inertia, overhauling loads of both induction and permanent magnet (PM) motors, gear-less drive applications and paralleling solutions.
Wall-mounted NXP drives are available in compact NEMA Type 1 (IP21) and NEMA Type 12 (IP54) enclosures.
The NXP wall-mounted units are equipped with internal EMC filtering with power electronics integrated into an all-metal frame. Smaller frame sizes (FR4-FR6) have an integrated brake-chopper as standard and the 380-500 Vac units can be equipped with an integrated brake resistor. Larger frames (FR7-FR12) can be equipped with an integrated brake-chopper as an option.
NXP drives are the smart drive of choice. With exceptional programming flexibility and fast fieldbus I/O the NXP drives can easily be integrated into any automation system.
Features
- Controls induction and permanent magnet motors
- Reliable, robust performance, engineered for demanding applications
- UL listed disconnected switch and ultra rapid AC fuses
- Frame 4 to Frame 6 includes integrated brake-chopper, Frame 7 to Frame 12 have integrated break-chopper as an option
- Wide array of I/O communication cards (OPT cards)
- Fast drive-to-drive communication
- DC-link bus terminal connections
- Dynamic open and closed loop vector control
- 50° C ambient rating, no derate
- Wall-mounted NXPs & option cards in SAI stock
Specifications
Main Connections
Input Voltage |
208…240 V; |
Input frequency |
45…66 Hz |
Connection to mains |
Once per minute or less |
Starting delay |
2 s (FR4 to FR8); 5 s (FR9) |
Network imbalance |
Max. ±3% of nominal voltage |
Supply Network
Networks |
TN, TT, IT |
Short circuit current |
Maximum short circuit current has to be < 100 kA. |
Motor Connections
Output voltage |
0–Uin |
Continuous output current |
IH: Ambient temperature max. +50°C, overload 1.5 x IH (1 min./10 min.) |
Starting current |
IS for 2 s every 20 s; After 2 s current controller forces it down to 150% IH. |
Output frequency |
0…320 Hz (standard NXP and NXS); |
Frequency resolution |
0.01 Hz (NXS); Application dependent (NXP) |
Control Characteristics
Control method |
Frequency control U/f |
Switching frequency (see parameter 2.6.9) |
NX_2/NX_5: Up to NX_0061: 1…16 kHz; Default: 10 kHz |
Frequency Reference Analogue input Panel reference |
Resolution 0.1% (10-bit), accuracy ±1% Resolution 0.01 Hz |
Field weakening point |
8…320 Hz |
Acceleration time |
0.1…3000 sec |
Deceleration time |
0.1…3000 sec |
Braking torque |
DC brake: 30% * TN (without brake option) |
Ambient Conditions
Ambient operating temperature |
FR4-FR9: |
Storage temperature |
–40°C…+70°C |
Relative humidity |
0 to 95% RH, non-condensing, non-corrosive, no dripping water |
Air quality - chemical vapours |
IEC 60721-3-3, unit in operation, class 3C2 |
Altitude |
100% load capacity (no derating) up to 1,000 m |
Vibration EN50178/EN60068-2-6 |
5…150 Hz |
Shock EN50178, EN60068-2-27 |
UPS Drop Test (for applicable UPS weights) |
Enclosure class | IP21/NEMA1 standard in entire kW/HP range IP54/NEMA12 option in FR4 to FR10 Note! Keypad required for IP54/NEMA12 |
Pollution degree |
PD2 |
EMC (at default settings)
Immunity |
Fulfils EN61800-3 (2004), first and second environment. |
Emissions |
Depend on EMC level. See chapters 2 and 3. |
Safety
|
EN 61800-5-1 (2007), CE, cUL, C-TICK; (see unit nameplate for more detailed approvals) IEC 60664-1 and UL840 in overvoltage category III. |
Emissions
Average noise level (cooling fan) in dB (A) |
FR4 44, FR9 76, FR5 49, FR10 76, FR6 57, FR11 76, FR7 57, FR12 76, |
Control Connections (OPTA1, OPTA2 and OPTA3)
Analogue input voltage |
0…+10 V, Ri = 200 kΩ, (–10 V…+10 V joystick control) Resolution 0.1%, accuracy ±1% |
Analogue input current |
0(4)…20 mA, Ri = 250 Ω differential |
Digital inputs (6) |
Positive or negative logic; 18…30 VDC |
Auxiliary voltage |
+24 V, ±10%, max volt. ripple < 100 mVrms; max. 250 mA Dimensioning: max. 1000 mA/control box (power backup) |
Output reference voltage |
+10 V, +3%, max. load 10 mA |
Analogue output |
0(4)…20 mA; RL max. 500 Ω; Resolution 10 bit; Accuracy ±2% |
Digital outputs |
Open collector output, 50 mA/48 V |
Relay outputs |
2 programmable change-over relay outputs |
Protections
Overvoltage trip limit |
NX_2: 437 VDC; NX_5: 911 VDC; NX_6: 1200 VDC |
Undervoltage trip limit |
NX_2: 183 VDC; NX_5: 333 VDC; NX_6: 460 VDC |
Earth fault protection |
In case of earth fault in motor or motor cable, only the frequency converter is protected |
Mains supervision |
Trips if any of the input phases is missing |
Motor phase supervision |
Trips if any of the output phases is missing |
Overcurrent protection |
Yes |
Unit overtemperature protection |
Yes |
Motor overload protection |
Yes* Motor overload protection provided at 110% of full motor load current. |
Motor stall protection |
Yes |
Motor underload protection |
Yes |
Short-circuit protection of +24 V and +10 V reference voltages |
Yes |
Models
VACON NXP is an air-cooled AC drive solution for all applications where robustness, dynamic performance, precision and power are required. This series of air-cooled drives can operate with anything from 0.37 kW to 160 kW.
380 - 500 Vac, 50/60 Hz, 3-Ph
Product Code |
Motor Shaft Power and Current |
Frame
Size |
|||||
Heavy Duty (150%) |
Normal Duty (120%) |
||||||
HP | kW | Amps | HP | kW |
Amps |
||
NXP0003-5A2H1-SSSA1A2 | 1 | 0.75 | 2.2 | 1.5 | 1.1 | 3.3 |
F4 |
NXP0004-5A2H1-SSSA1A2 | 1.5 | 1.1 | 3.3 | 2 | 1.5 | 4.3 |
F4 |
NXP0005-5A2H1-SSSA1A2 | 2 | 1.5 | 4.3 | 3 | 2.2 | 5.6 |
F4 |
NXP0007-5A2H1-SSSA1A2 | 3 | 2.2 | 5.6 | 5 | 3 | 7.6 |
F4 |
NXP0009-5A2H1-SSSA1A2 | 5 | 3 | 7.6 | 5 | 4 | 9 |
F4 |
NXP0012-5A2H1-SSSA1A2 | 5 | 4 | 9 | 7.5 | 5.5 | 12 |
F4 |
NXP0016-5A2H1-SSSA1A2 | 7.5 | 5.5 | 12 | 10 | 7.5 | 16 |
F5 |
NXP0022-5A2H1-SSSA1A2 | 10 | 7.5 | 16 | 15 | 11 | 23 |
F5 |
NXP0031-5A2H1-SSSA1A2 | 15 | 11 | 23 | 20 | 15 | 31 |
F5 |
NXP0038-5A2H1-SSSA1A2 | 20 | 15 | 31 | 25 | 18.5 | 38 |
F6 |
NXP0045-5A2H1-SSSA1A2 | 25 | 18.5 | 38 | 30 | 22 | 46 |
F6 |
NXP0061-5A2H1-SSSA1A2 | 30 | 22 | 46 | 40 | 30 | 61 |
F6 |
NXP0072-5A2H0-SSSA1A2 | 40 | 30 | 61 | 50 | 37 | 72 |
F7 |
NXP0087-5A2H0-SSSA1A2 | 50 | 37 | 72 | 60 | 45 | 87 |
F7 |
NXP0105-5A2H0-SSSA1A2 | 60 | 45 | 87 | 75 | 55 | 105 |
F7 |
NXP0140-5A2H0-SSSA1A2 | 75 | 55 | 105 | 100 | 75 | 140 |
F8 |
NXP0168-5A2H0-SSSA1A2 | 100 | 75 | 140 | 125 | 90 | 170 |
F8 |
NXP0205-5A2H0-SSSA1A2 | 125 | 90 | 170 | 150 | 110 | 205 |
F8 |
NXP0261-5A2H0-SSFA1A2 | 150 | 110 | 205 | 200 | 132 | 261 |
F9 |
NXP0300-5A2H0-SSFA1A2 | 200 | 132 | 245 | 250 | 160 | 300 |
F9 |
Frame Size and Weights
Dimensions (Inches) |
Weight |
Dimensions (mm) |
Weight |
|||||||||||||||||||||||
W | H | D | (lbs) | W | H | D |
(kg) |
|||||||||||||||||||
Frame 4 | 5 | 11.5 | 7.5 | 11 | 128 | 292 | 190 |
5 |
||||||||||||||||||
Frame 5 | 5.67 | 15.39 | 8.5 | 18 | 144 | 391 | 214 |
8 |
||||||||||||||||||
Frame 6 | 7.68 | 20.5 | 9.33 | 41 | 195 | 519 | 237 |
19 |
||||||||||||||||||
Frame 7 | 9.33 | 23.27 | 10.12 | 77 | 237 | 591 | 257 |
35 |
||||||||||||||||||
Frame 8 | 11.46 | 30 | 13.54 | 128 | 291 | 758 | 344 |
58 |
||||||||||||||||||
Frame 9 | 19 | 45.28 | 14.25 | 322 | 480 | 1150 | 362 |
146 |
Downloads